본문 바로가기 주메뉴 바로가기

Electric Power Equipment

VCB(Side Mount Type)

This device enhances stability by accommodating the Vacuum Interrupter (VI) within independently housed units for each phase. With 60% fewer parts than spring actuators, component failure and incorrect operation factors are reduced. Additionally, the PMA control circuit employs a Relay scheme, providing resilience against EMC and EMI.
  • Key Features

    - Withdrawable, each phase front and rear arrangement type (Side Mount Type)
    - Permanent Magnetic Actuator (PMA) Operating Mechanism
    - Features On-Off control with mechanically operable manual device
  • Application

    -Built-in Distribution Board
Product Specifications

 SJVP-20P-16/06

Applicable Standards
IEC62271-100
Rated Voltage
24kV
Rated Current
630A
Rated Frequency
60㎐
Rated Power Frequency Withstand Voltage
50kV / 1min
Impulse Withstand Voltage
125kV
Rated Breaking Current
16kA
Rated Making Current
41.6kAPEAK